A split structure can be adopted, with the refrigeration unit and the box placed separately;
The top of the box is perforated for easy lifting of the motor;
Box bottom has 4 support holes sealed with molded silicone plugs to prevent frost & water overflow.
The central axis adopts a special sealing device to avoid frosting at low temperatures;
Model | Studio Size (D*W*H)mm | Dimension(D*W*H)mm | |
LRHS-2000B-LJ | 1000×2000×1000 | Subject to contractual three-view | |
LRHS-4000B-LJ | 2000×2000×1000 | ||
LRHS-6000B-LJ | 2000×3000×1000 | ||
LRHS-8000B-LJ | 2000×2000×2000 |
temperature range | A:-20℃~150℃ B:-40℃~150℃ C:-60℃~150℃ D:-70℃~150℃ |
||||||
Temperature uniformity | ≤2℃ (at no load) | ||||||
Temperature fluctuation | ±0.5℃ (at no load) | ||||||
Time Setting Range | 1~60000M | ||||||
heating rate | -40℃~100℃≤90min | ||||||
cooling rate | 100℃~-40℃≤90min | ||||||
Outer case material | High quality A3 steel plate electrostatic spraying | ||||||
Inner box material | Imported high-grade stainless steel SUS304 | ||||||
Insulation material | Rigid polyurethane foam + fiberglass | ||||||
Temperature Controller | Imported “UEC” brand temperature meter | ||||||
temperature sensor | PT100 platinum resistance temperature measurement body | ||||||
Cooling method | Single or double cascade refrigeration | ||||||
compactors | France Tycon/Germany BITZER/Germany Gulen | ||||||
standard configuration | Emergency stop switch, three-color indicator light | ||||||
security protection | Compressor overpressure overload, over temperature, fan motor overheating, leakage protection Overall equipment phase/reverse phase, test timing, overload and short-circuit protection |
||||||
Supply Voltage | AC380V±10% 50Hz | ||||||
Power | (A)13.5kW/16.0kW/18.5kW/21.0kW (B)15.0kW/18.5kW/22.0kW/25.0kW (C)18.5kW/24.0kW/28.0kW/34.5kW |
||||||
operating environment | 5℃~+28℃ ≤85% RH | ||||||
Note: 1、the test data are used in the ambient temperature of 25 ℃ and well ventilated conditions measured 2、The above parameters are for reference only, and can be customized according to user-specific test parameters. 3、This technical information, subject to change without notice |