A split structure can be adopted, with the refrigeration unit and the box placed separately;
The top of the box is perforated for easy lifting of the motor;
Box bottom has 4 support holes sealed with molded silicone plugs to prevent frost & water overflow.
The central axis adopts a special sealing device to avoid frosting at low temperatures;
Model | Studio Size (D*W*H)mm | Dimension(D*W*H)mm | |
LRHS-101-ES | 450×450×500 | 1350×830×1120 | |
LRHS-225-ES | 500×600×750 | 1400×980×1370 | |
LRHS-504-ES | 700×800×900 | 1600×1180×1570 | |
LRHS-800-ES | 800×1000×1000 | 1700×1380×1670 | |
LRHS-1000-ES | 1000×1000×1000 | 1850×1380×1670 |
temperature range | 55℃~100℃ | ||||||
Temperature uniformity | ≤2℃ (at no load) | ||||||
Temperature fluctuation | ±0.5℃(at no load) | ||||||
Humidity range | 85%~98%RH (temperature 55℃~85℃) | ||||||
Humidity uniformity | +2% -3% RH | ||||||
Humidity fluctuations | ±2% | ||||||
heating rate | 1.0~3.0℃/min | ||||||
Time Setting Range | 1~9999H | ||||||
test hole | Mounted on the left side of the machine for use with external test power or signal cables | ||||||
viewing window | 210 x 275mm or 395 x 395mm (effective field of view) | ||||||
Outer case material | High quality A3 steel plate electrostatic spraying | ||||||
Inner box material | Imported high-grade stainless steel SUS304 | ||||||
Insulation material | Rigid polyurethane foam + fiberglass | ||||||
Temperature Controller | Korea Saintyear TEMI300 | ||||||
temperature sensor | PT100 platinum resistance temperature measurement body | ||||||
overtemperature protector | Korea RAINBOW | ||||||
standard configuration | 2 layers of sample racks, 1 roll of wet bulb gauze | ||||||
security protection | Over-temperature, fan motor overheating, overall equipment phase failure/reverse phase Water shortage protection, test timing, leakage protection, overload and short-circuit protection |
||||||
Supply Voltage | AC220V±10% 50±0.5Hz AC380V±10% 50Hz | ||||||
Power | 3.6kW/3.6kW/7.2kW/10.5kW/10.5kW | ||||||
operating environment | 5℃~+28℃ ≤85% RH | ||||||
Note: 1、 the above data are in the use of ambient temperature of 25 ℃ and well ventilated conditions measured 2、Can be customized according to the user’s specific test requirements non-standard constant temperature and humidity test chamber, constant temperature and humidity test chamber, etc. 3、This technical information, subject to change without notice |